American approaches each cleanroom design with a straightforward yet proven method in cleanroom principles. Whether you already have a preliminary drawing or need complete clean room design services, we can provide you with a cost effective system that meets your needs. All modular cleanrooms are designed in accordance with the appropriate clean room standard ISO 14644-1 / US Fed Std 209 as part of the overall clean room design service. Modular prefabricated clean rooms are factory engineered and designed to meet all your specifications for temperature, humidity, differential pressure, lighting, and noise levels. Our proprietary wall system can be designed and engineered to accommodate roof loads for storage or mechanical and process equipment.
|
|
American Cleanroom Systems provides clear and easy-to-read CAD generated drawings to help you visualize your cleanroom. |
American Cleanroom Systems offers state-of-the-art technology at competitive prices. |
|
Cleanroom Design Services
|
![]() |
Cleanroom Design Options
|
Cleanroom Design Guidelines
| SI | ISO 14644-1 | ROOM CLASS | Maximum allowable count per cubic foot of air. | ||||
| 0.1p | 0.2p | 0.3p | 0.5p | 5p | |||
| Class 1 | |||||||
| M1 | Class 2 | 0 | |||||
| M1.5 | Class 3 | 1 | 35 | 7.5 | 3 | 1 | |
| M2.5 | Class 4 | 10 | 350 | 75 | 30 | 10 | |
| M3.5 | Class 5 | 100 | 750 | 300 | 100 | ||
| M4.5 | Class 6 | 1,000 | 1000 | 7 | |||
| M5.5 | Class 7 | 10,000 | 10000 | 70 | |||
| M6.5 | Class 8 | 100,000 | 100000 | 700 | |||
All Guidelines and Criteria are approximates.
| CRITERIA | CLASS 10 M2.5 ISO 4 |
CLASS
100 M3.5 ISO 5 |
CLASS
1,000 M4.5 ISO 6 |
CLASS
10,000 M5.5 ISO 7 |
CLASS
100,000 M5.5 ISO 8 |
| Air Changes Per Hr / Min | Per Hour/Per Minute 500-600/8-10 | 300 To 480 5 To 8 |
180/3 | 60/1 | 30/.5 |
| Filter Coverage % | 90 to 100 | 50 to 70 | 20 to 30 | 7 to 15 | 4 to 5 |
| CFM Per Square Foot | 85 to 90 | 36 to 65 | 18 to 32 | 9 to 16 | 4 to 8 |
| Filter Efficiency | 99.9997 (5-9s ULPAs) |
99.997 (4-9s HEPAs) |
99.997 (4-9s HEPAs) |
99.997 (4-9s HEPAs) |
99.97 (3-9s HEPAs) |
| Type of Ceiling | 2" Aluminum Painted Grid | 2" Aluminum Painted Grid | 2" Aluminum Painted Grid | 1 1/2" T-Bar Conventional | 1 1/2" T-Bar Conventional |
| Light Fixture Type | Tear Drop or Flow Thru |
Tear Drop or 2'x4' C/R Fixture | 2' X 4' Cleanroom Fixture | 2' X 4' Cleanroom Fixture | 2' X 4' STD Fixture Field Sealed |
| Ceiling Panels | FRP or Epoxy Painted | FRP, Vinylrock or Mylar | Vinylrock or Mylar | Vinylrock or Mylar | Vinylrock or Mylar |
| Wall System | Modular | Modular | Modular | Modular or Drywall | Modular or Drywall |
| Floor Covering | Heat Weld Vinyl or Poured Epoxy | Heat Welded Sheet Vinyl | Solvent Welded Sheet Vinyl | Sheet Vinyl or VCT | Sheet Vinyl or VCT |
| Flooring Base | 2" to 6' Cove | Cove or Aluminum Base Channel | Cove or Aluminum Base Channel | Cove or Aluminum Base Channel | Cove or Aluminum Base Channel |
| Air Returns | Raised Floor or Center Returns | Low Wall on Long Axis | Low Wall at Perimeter | Low Wall | Low Wall or Ceiling |
All Guidelines and Criteria are approximates.